3 Phase Autotransformer for vertical mountingDAS 2.0 - 5.0kVA according to IEC/DIN EN61558-2-13

overviewtechnical dataPDF data sheet

Typical applications

3 phase autotransformer according to IEC/EN61558-2-13 for general applications without the need of a galvanic isolation, e.g. for transforming typical mains voltage to other voltages needed by tools, machinery or other devices.

Autotransformers do not provide any electrical protection due to the lack of galvanic isolation between input and output windings.

Specifications

3 phase transformer according to EN61558-2-13. protection class I ready. Due to innovative vacuum impregnation in polyester varnish, the noise level is extraordinary low. Screw terminals are contact proof according to BGV A3.

Autotransformers are provided for a voltage range from 100 V up to 550 V (special voltage versions on request).

Standard switching matrix: Yan0 (typical star load approx. 10%). If typical star load should reach rated current, switching matrix Zan0 is used.

Please add switching matrix requested when ordering the transformer. Final operation position must allow natural convection through coolant bore. For further information, don´t hesitate to contact us.

Core size > 3UI150/65 – 4.5 kVA: Transformer provides 2 loops for safe transportation or craning.

3 Phase Autotransformer for vertical mounting

with screw type terminal IEC/EN61558-2-13

Voltage range input / output 100 V … 550 V
Rated frequency 50/60 Hz
Power range 2,0kVA … 5,0kVA
Output design Schaltgruppe Standard YNa0

Sternpunktbelastbarkeit ca.10%

Schaltgruppe auf Anforderung ZNa0

Sternpunktbelastbarkeit 100%

Max. ambient temperature 40°C
UL Insulation System (optional) OBJY2.E181051
Insulation class (IEC85) B 130°C
Fire protection class UL94HB (V-0 possible)
Degree of protection IP00
Protection class I ready
  • No galvanic isolation
  • Natural convection between primary and secondary windingthrough coolant bores
  • Final operation position must allow natural convectionthrough coolant bores.
  • Ready for vertical mounting – including angle brackets
  • Transformer connections: Screw terminals according to BGV A3
  • Transformer completely vacuum impregnated
Rated 
power
kVA
Dimensions
approx. mm
Copper 
weight
KG


Total 
weight
KG


Size
Type and
Ordering No.
A
B
C*
D
E
F
2,0
245
130
207
185
81
9,0×13,0
6,30
19,30
3UI 120/51
DAS0200
2,5 265 130
227
200
76
10,0×18,0
7,50 20,50 3UI 132/46 DAS0250
3,2 265 145
227
200
90
10,0×18,0
8,20 25,50 3UI 132/60 DAS0320
4,0
300 150
260
224
94
10,0×18,0
12,20 31,80 3UI 150/52 DAS0400
4,5**
300 165
260
224
107
10,0×18,0
11,40
36,50
3UI 150/65 DAS0450
5,0**
335 155
290
248
110
10,0×18,0
17,00
44,00 3UI 168/58 DAS0500

Please note

*Dimension “C” indicates a reference value only. Phase current and therefore size of screw terminals used depends on transformer ratio (identical size). Coolant bore between primary and secundary winding. Winding on polyamide coil former.

**Transformer provides 2 loops for safe transportation or craning.

Explanation and vector-groups to applicate 1 phase and 3 phase autotransformers

Autotransformers do not provide galvanic isolation.

They have electroconductive connection between input and output winding. It`s not allowed to take autotransformers for electrically protective separation.

 

If difference between input voltage and output voltage is small:

  • mains power may be higher
  • transformed power is lower
  • size can be reduced (core, copper winding)

 

Since the high-voltage and low-voltage windings in an autotransformer share a common portion of the same winding, the size and material costs can be reduced.

Example shows 90% power saving compared to an isolating transformer

Equation to calculate the requested size

Example: 1 phase autotransformer / Input voltage 440 V / Output voltage 400 V / „Rated power“ needed for application 5 kVA

Identical equation works with 3 phase transformers.

 

 

 

 

Regarding input/ output “upper“ or „lower voltage“ is independant, voltage related only for 3 phase autotransformers value of phase voltage is important.

Standard circuit design of 3 phase autotransformers is YNa0. Max. load at neutral wire is approx. max. 10% of nominal current (phase current).

If 100% neutral wire load is requested, circuit design ZNa0 is manufactured.

Note: YNa0 design can be used in certain circumstances, if neutral wire at input provides full load and transformer star point is permanently connected to load. Please contact us for further informations!