1 Phase Control-/Isolating Transformer, Safety TransformerST 25-2500 VA IEC/DIN EN61558-2-2 /-4 /-6 and UL 1446

overviewtechnical dataPDF Data Sheet

1 phase control transformer

according to IEC/EN61558-2-2 for power supply of control circuits in machinery, terminal blocks (VDE0113/ EN60204).

Isolating transformer

according to IEC/EN61558-2-4 for general applications, e.g. electric (galvanic) isolation for devices according to VDE0700/ EN60335.

Safety transformer

according to IEC/EN61558-2-6 for general applications with double or enhanced insulation and max. 50V output voltage, e.g. electric (galvanic) isolation for devices according to VDE0805/EN60950.

Specifications

  • Due to the use of high quality insulating materials and special insulation design, ST series can be used as control-, isolating or safety transformer.
  • Our UL insulation system guarantees global application possibilities.
  • Inrush currents and short circuit behaviour are optimised for use with motor-circuit switches, especially equipped with primary circuit thermal or magentic switching functions.
  • Transformers are fully vacuum impregnated.
  • Screw terminals contact proof according to VBG4.
  • For voltage adjusting purposes, primary winding offers taps at ±5% of nominal input voltage.
  • Transformers are protection class I ready.
  • 2 blade terminals 6.3 x 0.8 for ground wire connection.
  • Mounting via angle brackets, any mounting position or angle possible.

 

 

 

1 Phase Control-/Isolating Transformer, Safety Transformer

according to IEC/EN61558-2-4-6

Input voltage

Input voltage 100 V … 600 V +/-5%
Output voltage 12 V … 600 V
Rated frequency 50/60 Hz
Output power 25 VA … 2500 VA
Max. ambient temperature 40°C
UL Insulation System B3 Standard
Insulation class (IEC85) B 130°C
Fire protection class UL94HB (V-0 möglich)
Open transformer
degree of protection
IP00
Protection class I
  • Welded ground wire connection 2 blade terminals 6.3 x 0.8 mm
  • Mounting via angle brackets in any mounting position or angle possible
  • Screw terminals contact proof according to BGV A3
  • Transformer completely vacuum impregnated

Overview: PRI 230V / SEK 24V (Yellow coloured rows: storage types)

Rated
power
VA
Short-time
power
at cos (phi)
0.5
VA
Short
circuit
voltage
Uk %
Rated
input
current
at 230V
Transformer
safety
switch
e.g. PKZM0
Dimensions
approx. mm
Cu
weight
KG


Total
weight
KG


Type and
Ordering No.
A
B
C
D
E
F
25 56 9,56 0,14 0,1-0,16/ 0,16 66 69 78 50 42 3,6×6 0,14 0,75 ST002230024
40 91 9,00 0,22 0,16-0,25/ 0,25 66 75 73 50 46 4,8×8 0,17 0,88 ST004230024
50 107 9,85 0,28 0,26-0,40/ 0,35 78 73 84 56 45 4,8×9 0,25 1,10 ST005230024
75 163 9,77 0,40 0,4-0,63/ 0,5 84 76 90 64 45 4,8×9 0,27 1,35 ST007230024
100 235 8,40 0,53 0,4-0,63/ 0,6 84 90 90 64 61 4,8×9 0,30 2,00 ST010230024
160 360 8,22 0,82 0,63-1/ 0,9 96 86 101 84 61 5,8×9 0,46 2,25 ST016230024
200 478 7,10 1,00 1-1,6/ 1,1 96 97 101 84 71 5,8×9 0,55 2,85 ST020230024
250 645 6,36 1,24 1-1,6/ 1,35 96 111 101 84 86 5,8×9 0,57 3,60 ST025230024
320 760 6,14 1,56 1,6-2,5/ 1,65 120 96 119 90 68 5,8×12 1,10 4,80 ST032230024

Overview: PRI 230V / SEK 24V (Yellow coloured rows: storage types)

Rated
power
VA
Short-time
power
at cos (phi) 
0.5
VA
Short 
circuit
voltage
Uk %
Rated
input
current
at 230V
Transformer 
safety 
switch
e.g. PKZM0
Dimensions
approx. mm
Cu
weight
KG
Total
weight
KG
Type and
Ordering No.
A B C D E F
25 55 9,58 0,09 0,1-0,16/ 0,1  66  69  78  50 42  3,6×6  0,14  0,75  ST002230024
40 90 9,56 0,14 0,1-0,16/ 0,14  66  75  73  50  46  4,8×8  0,17  0,88  ST004230024
50 106 9,98 0,16 0,16-0,25/ 0,17  78  73  84  56  45  4,8×9  0,25 1,10  ST005230024
75 165 9,49 0,23 0,16-0,25/ 0,24  84  76  90  64  45  4,8×9  0,27  1,35  ST007230024
100 233 8,50 0,30 0,25-0,4/ 0,35  84  90  90  64  61  4,8×9  0,30  2,00  ST010230024
160 358 8,35 0,47 0,4-0,63/ 0,55  96  86  101  61  61  5,8×9  0,46  2,25  ST016230024
200 480 7,00 0,57 0,4-0,63/ 0,63  96  97  101  84  71  5,8×9  0,55  2,85  ST020230024
250 647 6,18 0,71 0,63-1/ 0,8  96  111  101  84 86  5,8×9  0,57 3,60  ST025230024
320 752 6,27 0,91 0,63-1/ 1  120  96  119  90  68  5,8×12  1,10  4,80  ST032230024

Overview: PRI 230V / SEK 24V  (Yellow coloured rows: storage types)

Rated
power
VA
Short-time
power
at cos (phi) 
0.5
VA
Short 
circuit
voltage
Uk %
Rated
input
current
at 230V
Transformer 
safety 
switch
e.g. PKZM0
Dimensions
approx. mm
Cu
weight
KG
Total
weight
KG
Type and
Ordering No.
A B C D E F
25 55 9,26 0,09 0,1-0,16/ 0,1  66  69  78  50 42  3,6×6  0,14  0,75 ST002400230
40 94 8,95 0,14 0,1-0,16/ 0,14  66  75  73  50  46  4,8×8  0,17  0,88 ST004400230
50 112 9,15 0,16 0,16-0,25/ 0,17  78  73  84  56  45  4,8×9  0,25 1,10 ST005400230
75 166 9,10 0,23 0,16-0,25/ 0,24  84  76  90  64  45  4,8×9 0,28  1,35 ST007400230
100 244 7,80 0,30 0,25-0,4/ 0,35  84  90  90  64  61  4,8×9 0,32  2,00 ST010400230
160 370 7,70 0,47 0,4-0,63/ 0,55  96  86  101 84  61  5,8×9 0,49  2,25 ST016400230
200 482 7,15 0,57 0,4-0,63/ 0,63  96  97  101  84  71  5,8×9 0,52  2,85 ST020400230
250 670 5,60 0,71 0,63-1/ 0,8  96  111  101  84 86  5,8×9 0,67 3,60 ST025400230
320 817 5,30 0,91 0,63-1/ 1  120  96  119  90  68  5,8×12 0,97 4,10 ST032400230
400 1115 4,57 1,11 1-1,6/ 1,3 120 107 119 90 79 5,8×12 1,10 5,10 ST040400230
500 1395 4,40 1,37 1-1,6/ 1,5 135 110 130 104 86 5,8×12 1,43 6,30 ST050400230
630 1630 4,37 1,71 1,6-2,5/ 1,85 150 110 142 122 82 7×15 1,95 7,70 ST063400230
800 2245 3,88 2,15 1,6-2,5/ 2,3 150 126 142 122 98 7×15 2,10 9,70 ST080400230
1000 2568 3,67 2,68 2,5-4/ 2,9 174 114 156 135 86 7×15 3,10 11,20 ST100400230
1250 3255 3,9 3,29 2,5-4/ 3,4 174 128 156 135 102 7×15 3,20 12,70 ST125400230
1600 4560 3,28 4,19 4-6,3/ 4,3 174 138 156 135 108 7×15 3,45 14,40 ST160400230
2000 5395 3,19 5,24 4-6,3/ 5,4 192 138 175 150 104 10×18 4,20 16,40 ST200400230
2500 7020 2,86 6,49 6,3-10/ 6,6 192 154 175 150 120 10×18 5,10 20,30 ST250400230